HMP240
User's Guide M210300en
18
OPENED COVER OF THE HMP 243
X15
CHANGE OF SETTINGS
DISABLED
Figure 4.1 Location of the security lock jumper
When the security lock jumper is connected, some commands are not available
(see Chapter 5).
Should the application require variables that are not included in the
configuration of the transmitter, the user is invited to contact Vaisala or a
Vaisala representative.
4.3 Selecting the analogue outputs
The HMP240 transmitter can be ordered ready with the current or voltage
outputs required. If the outputs need to be changed, move the jumpers in con-
nector X15 into positions as shown in Figure 4.2.